Schedule 2 thresholds by sector: who counts as an operator of essential services

Schedule 2 of the NIS Regulations 2018 sets the thresholds that make an organisation an operator of essential services. The Cyber Security and Resilience Bill (CSRB) keeps them and adds two entries: data centres at 1 MW, or 10 MW for enterprise sites, and load controllers at 300 MW for system-balancing.

Last updated · Precursor Security
Where this stands

Status checked : the Bill passed the House of Lords on 2 November 2026 and returns to the Commons to consider Lords amendments (no date set). On 4 November 2026 the Commons extended its carry-over, so it lapses if not passed by the end of 29 April 2027. It is not yet law. References are to HL Bill 62 (as amended on Report), so wording and numbering may still change in the final Act. This guide is general information, not legal advice.

Key points

  • Meeting a Schedule 2 threshold makes you an OES automatically, and you must notify your regulator within three months.
  • Regulators can also designate organisations below the thresholds where disruption could be significant.
  • The Bill adds data centres (1 MW, or 10 MW enterprise) and load controllers (300 MW, system-balancing purposes).
  • Banks, education and retail are not Schedule 2 subsectors; the review in clause 66, added by the Lords, must consider more sectors.

What are the Schedule 2 thresholds?

They are the size tests in Schedule 2 to the NIS Regulations 2018 that decide who is an operator of essential services (OES). If you provide one of the services below and meet its threshold, you are deemed to be an OES under regulation 8(1). The Cyber Security and Resilience Bill (CSRB) amends these Regulations rather than replacing them, keeps every existing threshold, and adds two new entries for data centres and large load controllers.

The figures below are simplified from Schedule 2 on legislation.gov.uk, read on 2 November 2026. The legal wording includes definitions and exclusions, so check the original paragraph before deciding. Legislation.gov.uk also lists a pending change to one air transport definition (S.I. 2026/230), which does not affect a number. New entries are taken from HL Bill 62 (as amended on Report), which passed the Lords on 2 November 2026 and is not yet law.

How do you use the thresholds?

Find your service, check the threshold, then check how you are measured. Three routes lead to OES status:

  1. Deemed designation. You provide an essential service in the UK and meet the threshold (regulation 8(1)). Under the Bill this applies "whether or not the person is established in the United Kingdom" (new regulation 8(1ZA)).
  2. Notification. If you are deemed an OES, you must tell your designated competent authority within three months (regulation 8(2)). Data centres give fuller details to Ofcom under new regulation 8ZA.
  3. Designation below the threshold. A regulator can designate you anyway if an incident could have significant disruptive effects (regulation 8(3)).

If you are below every threshold and have not been designated, you are not an OES. You could still be an RDSP or RMSP, or a critical supplier.

Energy

Service Threshold Para
Electricity supply, Great Britain More than 250,000 final customers 1(2)(a)
Electricity supply with affiliated generation, Great Britain Generators with total input capacity of at least 2 GW 1(2)(a)
Electricity supply, Northern Ireland More than 8,000 consumers 1(2)(b)
Electricity generation, Northern Ireland At least 350 MW 1(2)(b)
Electricity transmission, Great Britain Could disrupt delivery to more than 250,000 final customers 1(4)(a)
Offshore transmission, Great Britain Connected generators of at least 2 GW 1(4)(a)
Electricity interconnectors, Great Britain At least 1 GW 1(4)(a)
Electricity distribution, Great Britain Could disrupt delivery to more than 250,000 final customers 1(5)(a)
Oil, upstream pipelines, processing and offshore installations, UK More than 3,000,000 tonnes of oil equivalent a year 2(2), 2(4), 2(6)
Oil transmission, Great Britain More than 500,000 tonnes a year 2(3)(a)
Oil transmission, Northern Ireland More than 50,000 tonnes a year 2(3)(b)
Oil facilities, Great Britain More than 500,000 tonnes of storage, production or supply 2(5)(a)
Oil storage, Northern Ireland More than 50,000 tonnes 2(5)(b)
Gas supply, Great Britain More than 250,000 final customers 3(2)(a)
Gas supply, Northern Ireland More than 2,000 customers 3(2)(b)
Gas transmission and distribution, Great Britain Could disrupt delivery to more than 250,000 final customers 3(3), 3(4)
Gas interconnectors, storage and LNG, Great Britain More than 20 million cubic metres a day into a transmission system 3(3), 3(5), 3(6)
Gas processing and production, UK More than 3,000,000 tonnes of oil equivalent a year 3(7), 3(8)

Transport

Service Threshold Para
Airports More than 10 million annual terminal passengers 4(2)
Air traffic services at airports Airports above 10 million annual terminal passengers 4(3)(b)
Air carriers More than 30% of passengers at such an airport, and more than 10 million in total across UK airports 4(4)
Shipping Over 5 million tonnes of annual freight at UK ports, and over 30% of the freight at a UK port that handles more than 15% of UK roll-on roll-off or lift-on lift-off traffic, more than 10% of liquid bulk or more than 20% of biomass fuel. Both limbs must be met 5(2)(a)
Passenger shipping Over 30% of passengers at a port with more than 10 million 5(2)(b)
Harbours, port facilities and vessel traffic services Ports with more than 10 million passengers, or ports above specified shares of UK freight traffic 5(3) to 5(5)
Metros, trams and light rail More than 50 million annual passenger journeys 6(4)
Road authorities and intelligent transport systems Roads carrying more than 50 billion vehicle miles 7

The freight shares in paragraph 5 are more than 15% of roll-on roll-off traffic, 15% of lift-on lift-off traffic, 10% of liquid bulk traffic, or 20% of biomass fuel traffic. Some rail and en-route air traffic entries have no number.

Healthcare and drinking water

Service Threshold Para
Healthcare No numeric threshold; depends on the provider types described 8
Drinking water Supply to 200,000 or more people 9

Digital infrastructure

Service Threshold Para
Top-level domain name registries 14 billion or more queries from UK devices in any 168-hour period 10(2)
DNS resolver services 500,000 or more different UK-used IP addresses in any 168-hour period 10(3)
Authoritative DNS hosting 100,000 or more domains registered to people with a UK address 10(3A)
Internet exchange points 30% or more market share among UK operators 10(4)

What would the Bill add?

Two new entries, both in HL Bill 62.

Service Threshold Schedule 2 paragraph Regulator
Data centre service Rated IT load of 1 MW or more 11(2) Ofcom
Enterprise data centre service Rated IT load of 10 MW or more 11(3) Ofcom
Load control Carries on activities for system-balancing purposes, and potential electrical control of 300 MW or more over relevant energy smart appliances 1(5A) DESNZ and Ofgem jointly (Government factsheet)

How is a data centre measured?

"Rated IT load" is the maximum electrical power available for the operation of the IT equipment housed in the data centre. It is not your actual usage. A "structure" includes a building, part of a building or a group of structures, so check how your site is drawn.

A data centre is run on an "enterprise basis" if you own or manage it for your own undertaking and its sole purpose is IT services for that undertaking. Enterprise sites get the higher 10 MW threshold. If you host anyone else, the 1 MW threshold applies. The Government's impact assessment estimated 64 data centre operators (businesses) would be in scope. See what is an enterprise data centre? and UK data centre regulations.

How is a load controller measured?

Add up the maximum flow of electricity into, and out of, all the relevant energy smart appliances you manage by load control signals, using manufacturers' stated capacities. Relevant appliances are electric vehicles, charge points, electrical heating appliances such as heat pumps and storage heaters, battery storage and virtual power plants. Intermediaries that can adjust your signals may count as load controllers too. Lords Committee added the system-balancing test, so purely commercial control outside that purpose is not enough. See large load controllers.

Worked examples

These are our reading of the text, not regulator decisions.

Scenario Threshold Likely position
Colocation provider with a 1.5 MW rated IT load site 1 MW In scope as a data centre OES
Bank running a 6 MW data centre only for its own IT 10 MW enterprise Below threshold
The same bank also renting racks to a partner 1 MW In scope: no longer solely for its own undertaking
Water company supplying 150,000 people 200,000 people Below threshold, unless designated
EV charging aggregator controlling 350 MW of charge points for grid balancing 300 MW In scope as a load controller
Regional airport with 4 million passengers 10 million passengers Below threshold, unless designated

What is not in Schedule 2

  • Banks and financial market infrastructure. Neither is a subsector. See does DORA apply to UK firms? for financial rules.
  • Cloud, online marketplaces and search engines. These are RDSPs with their own test.
  • Managed service providers. These are RMSPs with their own test.
  • Public telecoms networks and services. These are carved out of OES status under the Bill (new regulation 8(1A)).
  • Education, retail and most of the public sector. None is a Schedule 2 subsector. The Lords added a review under clause 66 of HL Bill 62 that must consider bringing in more sectors, including education, research and large-scale retail of essential goods.

Can the thresholds change?

Yes. The Government's data centre factsheet says thresholds can be adjusted over time, and clause 29 regulations under the Bill can change the regime more widely, after consultation and approval by both Houses. The clause 66 review, if it survives the Commons, must report within 12 months of Royal Assent on whether more sectors should be in scope. See the secondary legislation tracker.

What happens once you are an OES?

You take on the full set of OES duties: security measures, incident reporting, regulator information requests, inspections and penalties. Today, incidents must be notified no later than 72 hours after you become aware, and the maximum penalty is £17 million. Once the Bill's changes commence, you would give an initial notification within 24 hours and a full notification within 72 hours of becoming aware of an incident with an actual adverse effect, and penalties would rise to up to the greater of £17 million and 4% of turnover. Find your regulator in which regulator covers you.

Sources

Frequently asked questions

You are deemed to be an operator of essential services under regulation 8(1) of the NIS Regulations, and must notify your designated competent authority within three months. Under the Bill this applies whether or not you are established in the UK. You then take on OES duties, including security measures, incident reporting (no later than 72 hours today, or 24-hour initial and 72-hour full notifications under the Bill) and regulator oversight.

Yes. Under regulation 8(3), a designated competent authority can designate an organisation that does not meet a threshold if an incident affecting it could have a significant disruptive effect on an essential service. The Bill adds that this applies whether or not the organisation is established in the UK. Designation is by written notice.

By rated IT load: the maximum electrical power available for the IT equipment housed in the data centre, not actual usage. A structure can be a building, part of one or a group of structures. The threshold is 1 MW, or 10 MW where the data centre is run solely to provide IT services for its owner's own undertaking.

No. Neither the NIS Regulations 2018 nor the Bill includes a banking or financial market infrastructure subsector. UK banks are regulated for operational resilience by the FCA and PRA instead. A financial group could still be caught by the Bill through another activity, such as providing a cloud or managed service, or running a large data centre.

Yes. The Government's data centre factsheet says thresholds can be adjusted over time, and clause 29 regulations can change the regime after consultation and approval by both Houses. If clause 66 survives the Commons, the Government must review within 12 months of Royal Assent whether more sectors, such as education and large-scale retail, should come into scope.